Podłogówka słabo grzeje? Przyczyny i za mały przepływ

The boiler is running, the thermostat is calling for heat, but the living room floor is barely warm. Or the underfloor heating warms unevenly: it’s warm by the wall but cool in the middle of the room. When underfloor heating isn’t heating well, the installer usually finds the cause in the boiler room or at the manifold, not under the floor.

Underfloor heating that isn’t heating well is often caused by low water flow through the loops, not by a fault with the pump itself. That’s why we start troubleshooting at the manifold: air, flow meters, filter, actuators, and mixing valve. We check the pump last.

We explain in this guide how to narrow down the problem in just a few minutes, how much water should flow through a loop, and what to do when the flow is good but the floor is still cool.

Table of contents

  1. Flow or heat source? How to narrow down the problem
  2. Low flow in underfloor heating: what to check step by step?
  3. How to adjust flow meters? How much water should flow through the loop?
  4. The flow is good, but the floor is cool. What next?
  5. Frequently asked questions

Flow or heat source? How to narrow down the problem

Before concluding that the underfloor heating is weak throughout the house, narrow down the problem by touching the manifold bars. A hot supply bar and a cold return from one loop may indicate low flow in that loop. If the supply bar itself is cool, the problem may lie with the heat source, controls, or mixing valve upstream of the manifold.

Symptoms of underfloor heating that isn’t heating well
Symptom Most likely cause What to check first
One loop’s flow meter reads zero, supply is hot Actuator closed or valve insert stuck Actuator and valve insert pin
The float jumps, and you can hear gurgling Air in the loop Bleeding the loops
All loops have low flow Clogged filter, mixing valve with low Kvs, pump Filter, mixing valve, pump
Short loops are hot, long ones are cool No balancing Flow meter settings
The pump in the group keeps switching off The safety thermostat is shutting off the pump Supply temperature
Flow rates are normal, but the floor is cool Supply temperature too low or floor screed too thick Power supply and type of flooring

Low flow in underfloor heating: what to check step by step?

We check for low flow in the underfloor heating system in a set order, starting with the simplest and least expensive causes and ending with the pump. Each step takes a few minutes.

  1. Air in the loops. An air-locked loop gurgles, the flow meter float jumps, and the floor heats unevenly. Air can stop the flow completely even when the pump is running, which is why loops are bled one at a time, following the procedure described in the guide how to bleed underfloor heating step by step.
  2. Flow meter settings. Flow meters opened all the way send water through the short loops, leaving the longer ones underheated. This is the most common reason underfloor heating warms unevenly. The next section shows how much water should flow through each loop.
  3. Filter and dirt separator. If the flow has dropped across all loops at once, the filter upstream of the pump group or manifold is usually clogged, especially after the first heating season or after connecting underfloor heating to an old system. Magnetic filters that protect the heating system from deposits capture sludge and magnetite from the system. Shut off the valves and lower the pressure before opening the filter.
  4. Actuators, valve inserts and mixing valve. Actuators on the manifold are usually normally closed, so without a signal from the thermostat, the loop remains inactive. If the loop doesn’t start flowing after removing the actuator, the valve insert is stuck or damaged and usually needs to be replaced. If the flow is poor throughout the entire circuit, it may be restricted by a mixing valve with too low a Kvs value.
  5. Pump. Finally, check whether the pump is actually moving water: does the flow change when you change the speed, and do the pipes downstream of the pump warm up? If a pump moves just as little water at every speed despite being bled, it needs to be checked and often replaced. We describe other faults in the article on symptoms of a circulation pump malfunction.

A mixing valve is often the surprising culprit. The same scenario comes up repeatedly on installer forums: the flow meters show a fraction of the calculated flow, the pump is running at full speed, and after replacing just the valve, the flow rates increase noticeably. This comes down to a simple relationship: the pressure drop across the valve increases with the square of the flow rate. At 0.9 m³/h, a valve with a Kvs of 1.6 loses about 0.32 bar, while a valve with a Kvs of 4 loses only about 0.05 bar.

With an electronic pump, it’s also worth checking the operating mode. Underfloor heating usually uses constant differential pressure mode, described in the article on circulation pump operating modes. A higher speed will provide a little more flow, but it won’t replace balancing the loops.

Disconnect the actuators and pump from the power supply before removal, and only work on the filter when the system has cooled down.

How to adjust flow meters? How much water should flow through the loop?

Each loop should carry as much water as its output requires:

flow rate [l/min] = loop output [W] / (69.8 × ΔT [K])

What each value means:

  • Flow rate [l/min]: the amount of water that should flow through the loop per minute. Set this value on the flow meter.
  • Loop output [W]: the amount of heat the loop is expected to deliver to the room. You can find it in the heating system design or in the heat demand calculations for the room.
  • ΔT [K]: the temperature difference between the water in the loop’s supply and return lines. A difference of 1 K is equal to a difference of 1°C, so with a supply temperature of 35°C and a return temperature of 30°C, ΔT is 5 K.
  • 69,8: the conversion constant for water. It is based on the specific heat and density of water and the conversion of hours to minutes, so you always enter the same number.

W In practice, ΔT of approx. 5 K is assumed. Example: a loop with a power of 600 W requires 600 / (69.8 × 5) = approx. 1.7 l/min.

Flow rate in the loop and its output
Loop output Flow at ΔT 5 K Flow at ΔT 7 K
400 W 1.15 l/min 0.82 l/min
600 W 1.72 l/min 1.23 l/min
800 W 2.29 l/min 1.64 l/min
1000 W 2.87 l/min 2.05 l/min

Setting all flow meters to the same value is a common mistake. A loop in a large living room needs more water than a loop in a small bathroom, so with equal settings, the living room will be underheated. Start by partially closing the shortest loops, then check the difference between the supply and return temperatures once the system has warmed up.

How to read the scale depends on the manifold model, so always check its manual. You can find manifold types with flow meters and their documentation in the manifolds and pump groups for underfloor heating category.

The flow is good, but the floor is cool. What next?

If the flow rates on the flow meters are correct but the underfloor heating still does not heat well, the cause is usually an insufficient supply temperature or excessive thermal resistance in the floor finish. W underfloor heating design, the resistance of the finishing layer is assumed not to exceed approximately 0.15 m²·K/W. A thick carpet or panels on a thick underlay can exceed this limit.

If these are correct too, the issue is with the design. Loops that are too long (for 16×2 pipe, the usual maximum is 100 to 120 m), a supply pipe to the manifold that is too narrow, or too many loops on one circuit result in a flow rate the pump cannot deliver at a reasonable pressure difference. Adjustment only mitigates such errors. We discuss separately how loop resistance affects circulator pump selection for underfloor heating.

Call an installer when:

  • the pump is not pumping despite having power,
  • a leak has appeared at the manifold,
  • the pressure is dropping with no visible leak,
  • you suspect an error in the loop design,
  • electrical installation work is required.

Frequently asked questions

Why is the underfloor heating not heating well?

Most often, it’s due to insufficient flow in the loops: air, incorrectly set flow meters, a clogged filter, or a closed valve. Less often, the pump is to blame or the supply temperature is too low.

Why is one underfloor heating loop not heating, while the flow meter reads zero?

Usually, the actuator is not opening the loop, or the valve insert on the manifold is stuck or damaged. Less often, the loop is airlocked.

Will a higher flow rate through a loop produce proportionally more heat?

No. Doubling the flow rate increases the loop’s output by much less than twofold, while resistance and noise increase, so the flow rate should be calculated based on the loop’s requirements.

Will increasing the pump speed improve underfloor heating?

Only a little. W an unbalanced system, excess water will flow through the short loops, while the long ones will remain cool.

Can underfloor heating that heats poorly be improved without tearing up the floor?

Yes, in most cases, because the causes are in the boiler room or at the manifold. Only design errors, such as loops that are too long, require reconstruction.

Dambat - a trusted manufacturer of pumps and hydrotechnical equipment with quality certifications.

 

Awaria, Ogrzewanie, Pompa do co, Pompy, Pompy obiegowe