Wastewater pumping stations
DAMBAT offers residential pumping stations for sewage and rainwater for a wide range of applications. Domestic wastewater, leachate, dirty water, rainwater, etc. The target customers are individuals, small housing associations, and businesses. We manufacture residential pumping stations in two versions. PDM single- and twin-pump units with pumps lowered along guide rails and suspended on a coupling foot. PDA units with free-standing pumps at the bottom and rigidly connected pipelines. At customers’ request, we can manufacture special versions according to individual requirements.
What sets DAMBAT residential sewage pumping stations apart:
- High-density polyethylene PEHD tanks with internal diameters of Ø800mm and Ø1000mm and heights from H=2 – 3m.
- DN50/PE63 discharge risers made of materials resistant to the aggressive sewage environment,
- Each pump has an individual ball check valve for sewage (not a poppet, flap, or other…but a ball check valve, best suited for sewage containing feces and solids),
- We install a shut-off valve (full-bore ball valve) on each discharge riser, allowing the pump to be removed for servicing or the check valve to be serviced,
- W PDM versions come standard with a Storz coupling with a 2″ fire hose connection and shut-off valve for emergency connection of a DN50 fire hose and, for example, flushing the discharge pipeline at high pressure,
- A wide range of pumps we use for various applications:
- with a free passage under the impeller of 30-50mm, e.g. IBO VOX 50, DRENO Compatta, DRENO Alpha V,
- with a radial grinding system, Kraken 1800 DF, IBO WES, DRENO GRIX,
- with an axial grinder, DRENO GX and DRENO G2,
- with cutting impellers, IBO ZWE, IBO ZWQ, etc.
- with a disc grinder, such as KRAKEN 1800,
- with single-channel impellers, WQ Professional
- for dirty water and treated sewage: DRENO BIC, DRENO AM-AT, DRENO APX, WQ PRO, SWQ PRO,
- or high-pressure pumps such as the UP60/80,
- Control systems range from the simplest, with a float switch built into the pump, to advanced systems that alternate the operation of two pumps and signal faults. The systems are available for both single-phase 230 V and three-phase 400 V power supplies.
- Our residential pumping stations arrive at the customer’s site complete, assembled and ready to operate. Simply lower (bolt on) the pump and connect the power supply.
Differences between the PDM and PDA versions of the sewage pumping station:
PDM-type pumping station

Professional solutions for domestic pumping stations are drawn from municipal network pumping stations. The pump, fitted with a bracket, is lowered to the bottom of the station along two stainless-steel guide rails, where it engages with the coupling foot under its own weight. There is no need to enter the tank to lower and install the pump. Precisely made castings and machined surfaces on the foot and bracket fit together perfectly, ensuring a tight seal and proper connection. In our PDM pumping stations, we use only systems with two guide rails, so the pump does not rotate as it is lowered. The pump always aligns perfectly with the coupling foot, even when the pumping station tank is completely full of wastewater. Imagine you have removed the pump for cleaning or servicing, and a lot of wastewater has flowed in while it was out. You can't see where to position the pump. With two guide rails, that's not a problem, because the pump will still settle correctly onto the coupling foot.
In the PDM domestic pumping station, the ball check valve always remains inside the station, so wastewater from the pressure pipeline never flows back into the tank. We always install a Storz coupling on the vertical pressure pipe for flushing the pipeline. Small-diameter pipelines with low flow rates can sometimes become coated with sediment and clogged by solids carried along with the wastewater, such as sand, rags, wipes, or other solid matter. In that case, simply connect a hose from a vacuum truck or hydrant to the fire brigade coupling and open the shut-off valve in the pumping station. The high pressure and flow can quickly clear the pipeline and restore its functionality.
We currently offer the following most popular versions of PDM domestic pumping stations: PDM8-22-1, PDM8-25-1 and PDM10-25-2. The numbers 8 and 10 indicate the tank’s internal diameter, Ø800 and Ø1000 mm; 22 and 25 indicate tank heights of 2.2 and 2.5 m; and 1 and 2 indicate the number of pumps installed.
PDA-type pumping station

A domestic pumping station version with a simple, durable design that allows the pump and ball check valve to be quickly removed. With the PDA pumping station, the shut-off valve is located at the top of the tank to make it easy to stop wastewater from flowing back from the discharge pipe. The quick coupling lets you remove the entire discharge pipe riser along with the pump and ball check valve. There is no need to enter the pumping station to disconnect the pump or clean the ball check valve. The rigid pipe allows high-pressure wastewater pumps with heads of up to 40-80 m to be used, as there is no risk of the pump lifting off the guide rail coupling foot, as can happen in PDM pumping stations. All discharge pipe components are made from materials resistant to the aggressive wastewater environment (PE pipes, PE elbows, 304 stainless steel shut-off valve).
Standard dimensions for PDA pumping station tanks are: an internal diameter of Ø800 and heights of H = 2.2 m, H = 2.5 m and H = 2.7 m. For tanks with an internal diameter of Ø1000, we use heights of H = 2.5 m and H = 3 m. Other heights are available by arrangement.
Thanks to their simple design, PDA pumping stations are an attractive alternative for customers seeking budget-friendly solutions that meet the requirements of a modern pumping station for individual use.
Control options for domestic pumping stations:
We offer pumps with different power ratings, power supply options and control systems to suit our customers’ needs and preferences. Our range includes dozens of pump types powered by 230 V single-phase and 400 V three-phase supplies. Pumps are switched on either by a built-in float switch or by external float switches connected to dedicated controllers. We offer M121/M131 controllers or professional SPP control cabinets with a full set of safety features and a wide range of functions, such as three floats: dry-run, start-stop and alarm. When extreme conditions occur, an audible and visual alarm is activated to alert the user to problems with the pumping station system.
Each of our pumping stations has a modular design, so if any component is damaged, it can always be replaced with a new one.