Part of the room is warm, part is cold, something is gurgling in the manifold cabinet, and the flow meter float is at zero. This is what underfloor heating with trapped air most often looks like, especially after the system has been filled for the first time or work has been done on the manifold.

You bleed underfloor heating at the manifold by flushing the loops one at a time: with the boiler switched off and cooled down, the circulation pump off, and the valves to the boiler closed, you feed water in through the valve on the supply manifold and let it out through the valve on the return manifold until no more bubbles come out of the hose. If the manifold is the highest point in the system, it’s often enough to leave one loop open and let the pump push the air out through the air vent.

W this guide, we explain both methods, how to safely refill the system, and what to do if air keeps coming back.

Table of contents

  1. How to bleed underfloor heating step by step
  2. Bleeding underfloor heating yourself: from the tap or with a flushing station?
  3. Underfloor heating air bleeding with the pump: on or off?
  4. How can you tell if there is air in the underfloor heating system?
  5. Manifold: which bar is the supply and which is the return?
  6. Unusual systems: no air vent, with an RTL valve, supplied by a radiator
  7. What pressure should I set after bleeding underfloor heating?
  8. Why does air keep getting into the underfloor heating system?
  9. When should you call an installer?
  10. Frequently asked questions

How to bleed underfloor heating step by step

You bleed underfloor heating by flushing the loops one at a time through the manifold: water enters through the valve on the supply manifold and exits through a hose connected to the valve on the return manifold, while the boiler and circulation pump are switched off. W this way, you can bleed underfloor heating in any system, even when the manifold is lower than the loops.

What should you prepare before bleeding the system?

You’ll need two hoses that fit the manifold valves, a bucket, a towel, and a bleed key. Spread the towel or plastic sheet on the floor under the manifold cabinet, as a little water may spill when connecting and disconnecting the hoses. Also check whether the system contains glycol or inhibitor fluid: this fluid must not be poured down the drain, and work on the system should be carried out by an installer.

Step-by-step procedure

  1. Turn off the boiler and circulation pump and wait for the system to cool down.
  2. Take a photo of the settings on the flow meters and heads so you can restore them afterward without guessing.
  3. Close the isolation valves between the manifold and the boiler. This prevents mains water pressure from reaching the boiler and opening the pressure relief valve.
  4. Close all loops on the supply and return manifolds.
  5. Connect the hoses: the supply hose to the fill valve on the supply manifold, and the drain hose to the drain valve on the return manifold. Place the end of the drain hose over a drain or in a bucket.
  6. Open the drain valve, then slowly open the supply valve.
  7. Open one loop on both sides of the manifold.
  8. Flush until water flows steadily from the hose, without bubbles or noise. A long loop takes longer than a short one.
  9. Close the loop and move on to the next one, repeating steps 7 and 8.
  10. Turn off the water supply, then close the drain valve.
  11. Disconnect the hoses, open the loops and isolation valves, and restore the settings from the photo.
  12. Bleed the manifold rails using the air vents, top up the pressure through the boiler filling valve to the value specified in the manual, check the boiler pressure gauge, and turn on the heating.

Through the supply or return?

Feed the water through the supply rail and drain it through the return rail, so the loop is flushed in the direction of normal operation. The flow meters and valve inserts then operate as designed. If the filling valve is only on one rail, follow the manifold instructions.

Most common mistakes when flushing loops

  • Flushing with all loops open: water takes the shortest route, leaving air in the long loops.
  • Leaving the valves to the boiler open: mains pressure opens the safety valve.
  • Filling too quickly, which carries air along instead of pushing it out.
  • Flushing a hot system.
  • Leaving the hose connected to the tap after finishing.
  • Forgetting to bleed the manifold rails at the end.

Bleeding underfloor heating yourself: from the tap or with a flushing station?

You can bleed underfloor heating yourself using a hose from the tap, but only through a connection with backflow protection compliant with PN-EN 1717. Water from the heating system must not flow back into the drinking water supply, and a hose connected to a tap could draw it in if the mains pressure temporarily drops.

A regular shut-off valve is not this kind of protection. Disconnect the hose from the tap immediately after use, and have a technician install permanent system filling points.

Tap water also poses a risk to the system itself. Every amount of fresh water introduces oxygen, which speeds up corrosion of steel components, as well as calcium and magnesium compounds, which form limescale deposits on the boiler heat exchanger. A one-time flush is not a problem, but frequent top-ups and repeated flushing with mains water will reduce boiler efficiency and shorten pump life over time. So the less fresh water that enters the system, the better, and you should check the boiler manual for the requirements for heating water quality.

An alternative is flushing in a closed loop: water circulates from a tank through the loop and back to the tank, while air escapes at the open surface. This introduces less fresh water into the system, and bubbles are easy to monitor.

Underfloor heating air bleeding methods
Method Advantages Limitations
Hose from the tap through a protected connection Low cost, high flow rate Plenty of fresh water, requires drinking water protection
Flushing station with tank Closed loop, easy to monitor bubbles Equipment cost or rental
System circulation pump No additional equipment Works only when the manifold is the highest point

Underfloor heating air bleeding with the pump: on or off?

When flushing with water through the manifold, the circulation pump and boiler must be switched off. Switch on the pump only if the manifold is the highest point in the system and one loop is open.

What does it mean for the manifold to be at the highest point? The manifold bars with air vents must be higher than all the loop pipes, as in a typical cabinet mounted on the wall above the floor on the same story. Air always rises, so the pump pushes bubbles out of the loops, where they collect in the manifold and escape through the air vent. If the manifold is lower, for example in a basement boiler room, while the loops are on the ground floor, air will become trapped at the highest point of the loop, and the pump will not push it down to the manifold.

W this method, one open loop receives the pump's full flow, which pushes air out through the air vent on the manifold. Set the pump to its highest speed while bleeding, and if it has a separate bleeding function, you can use it according to the instructions. However, do not leave the pump running with all loops closed unless the system has a bypass, as the pump would then be working against a closed valve. Also watch out for air in the pump itself: if it is noisy or not pumping, first bleed the central heating circulation pump

Which method to choose
Situation Method Circulation pump
Manifold at the highest point, several cold loops Pumping it through Switched on, one loop open
Manifold in the boiler room, loops higher up Flushing through the manifold Switched off
New system or after draining Flushing through the manifold Switched off
After servicing the manifold Flushing through the manifold Switched off
Pump did not help after two attempts Flushing through the manifold Switched off
System with glycol or inhibitor Installer Not applicable

How can you tell if there is air in the underfloor heating system?

You can tell that underfloor heating has air in it if some loops are cold or heat in strips, you hear gurgling in the manifold or floor, and the loop flow meter reads zero even though the pump is running.

  • Some loops are cold or the floor heats in strips.
  • Gurgling and noise in the manifold or under the floor.
  • The loop flow meter stays at zero or the float jumps.
  • Pressure drops after the pump starts or after bleeding.
  • Pump is noisy.

If the pressure on the gauge is persistently too low, start by adding water. We describe the symptoms in the article about what happens when there is too little water in the central heating system. If the floor still heats poorly after bleeding, the cause is usually the flow or loop settings, not air.

Manifold: which bar is the supply and which is the return?

The supply manifold is the one connected to the pipe from the boiler or pump group, and it is warmer when the heating is running. It usually has flow meters, while the return manifold has inserts for actuators or thermostatic heads. However, the layout can be reversed, so if in doubt, follow the manifold instructions.

Manifold components and bleeding
Element Where is Role in bleeding
Supply manifold Usually the upper one, with flow meters Water flows in here
Return manifold Usually the lower one, with inserts for actuators Water flows out here
Shut-off valves At the connection from the boiler Closed during flushing
Fill-and-drain valve At the end of the manifold Hose connection
Air vent At the end of the manifold Removes air collected in the manifold
Loop valve or flow meter On each loop You open one loop at a time

An air vent on the manifold removes only the air that reaches the manifold. Air must be pushed out of the loop itself by the flow. See what manifolds, flow meters, and air vents look like in the underfloor heating manifolds and pump groups category.

Unusual systems: no air vent, with an RTL valve, supplied by a radiator

W unusual systems, the principle is the same: the flow must push the air to a point where it can be released, namely a drain valve or the nearest air vent.

How do I bleed underfloor heating without an air vent?

If there is no air vent, remove the air by flushing the loops through the manifold drain valves or through the nearest vent in the system, for example at the boiler. A permanent solution is to have an installer fit an automatic air vent on the manifold.

How do I bleed underfloor heating with an RTL valve?

To bleed a single loop with an RTL valve, which limits the temperature of its return, first set the valve to maximum. Release the air through the vent in the valve box, if it has one, or flush the loop after isolating it. Always check the valve manual for the correct procedure.

Underfloor heating supplied by the radiator system or located on another floor

Air rises to the highest point in the system, so bleed radiators starting with the lowest and moving up to the highest. Air released from the lower radiators moves up through the system, so if you started at the top, you would have to go back there later. Starting at the bottom lets you collect the air as you go and ultimately remove it at the highest point, following the instructions in the guide how to bleed a radiator step by step. If the manifold is lower than the loops, the pump will not push the air upward, so the loops need to be flushed.

What pressure should I set after bleeding underfloor heating?

After bleeding, top up the pressure to the value specified in the boiler manual. For a single-family home, this is approximately 1.0 to 1.5 bar when cold, and the pressure rises slightly once the system heats up.

Low pressure encourages air to be drawn in through vents at the highest points, while excessive pressure opens the safety valve. Pressure usually drops after bleeding, so check the pressure gauge again after a few hours of operation.

Pressure check
When What to check What to do
Before bleeding Pressure gauge reading Record the value
After flushing and opening the valves to the boiler, when cold Value specified in the boiler manual Top up using the boiler's filling valve
After heating up Pressure increase Normal, if below the safety valve threshold
After 2 to 3 days of heating Pressure drop Bleed the manifolds and top up

Why does air keep getting into the underfloor heating system?

Fresh water releases dissolved gases during the first heating cycle because their solubility decreases as the temperature rises. Therefore, bleed the manifolds again after 2 to 3 days of operation and check the pressure. If air keeps returning, there is a fault:

  • low system pressure,
  • an incorrectly pressurized or damaged expansion vessel, which we explain how to check in our guide how to pressurize an expansion vessel in a central heating system,
  • a leak and frequent topping up with fresh water,
  • a faulty automatic air vent,
  • in older systems, pipes without an oxygen barrier (oxygen diffusion and corrosion).

As a routine check, simply check the pressure and bleed the manifolds before each heating season.

When should you call an installer?

Call an installer if you cannot carry out the procedure yourself or it does not work:

  • the system is filled with glycol or an inhibitor,
  • the manifold has no shut-off and drain valves,
  • there is a leak at the manifold,
  • the pressure keeps dropping despite topping it up,
  • a loop is still cold after flushing and the flow meter reads zero,
  • there is no safe filling point connected to the drinking water supply.

Frequently asked questions

Can you bleed underfloor heating yourself?

Yes, if the manifold has shut-off and drain valves and the system does not contain glycol or an inhibitor. All you need are two hoses and to flush one loop at a time.

When bleeding underfloor heating, should water be fed in through the supply and drained through the return?

Yes, water is fed in through the supply manifold and drained through the return manifold. Flush one loop at a time.

Should the circulation pump be on when bleeding underfloor heating?

Not when flushing with water: the pump and boiler must be switched off. Switch on the pump only if the manifold is at the highest point and one loop is open.

Is it normal for underfloor heating to get air in the system?

Yes, but only during the first few days of heating after filling with fresh water. If air keeps returning, the cause is usually low pressure, a leak or a faulty expansion vessel.

How often should you bleed underfloor heating?

Once before the heating season and after every refill, then again 2 to 3 days after start-up. If you need to do it more often, there is a fault.

Dambat - a trusted manufacturer of pumps and water engineering equipment with quality certifications.

 