The pump is running, the boiler is heating, but the radiators are barely warm. Or the opposite: the pump is off, but the rooms are still warm because the water is circulating by itself. WIn either case, it is worth taking a look in the boiler room at the inconspicuous component by the circulation pump: the check valve.
WIn a central heating system, install the check valve after the circulation pump, on the discharge side, with the arrow on the valve body pointing in the direction of flow, just like the arrow on the pump. Installing it before the pump in a closed system usually will not damage it, but adds resistance on the suction side and makes servicing more difficult. It is different in a hot, open system with a solid-fuel boiler: there, a valve before the pump can actually damage it.
WThis guide explains how to choose a valve for your type of system, install it correctly, and recognize when something has gone wrong.
Table of contents
- Check valve before or after the circulation pump?
- Which way should you install a check valve?
- Which check valve for which system?
- Symptoms of an incorrectly installed check valve
- How do you check a check valve step by step?
- Is a check valve needed for a central heating boiler?
- Why does a check valve knock?
- Does a check valve before the pump cause cavitation?
- How many check valves per circuit?
- Frequently asked questions
Check valve before or after the circulation pump?
After the pump. WIn a central heating system, install the check valve on the discharge side, as close to the pump as possible and before the shut-off valve. The reason is simple hydraulics: it is much easier for the pump to push water through a valve than to draw it through the extra resistance on the suction side.
What is this component for? A check valve has one job: a check valve prevents backflow when the pump is off. WIn practice, a check valve protects the system from two things: uncontrolled gravity circulation, which heats the house when it should not, and flow between parallel circuits, such as heating and domestic hot water tank charging.
Before installing a check valve, check whether the boiler or pump group already has one inside. A second valve will not improve anything; it will only add resistance that the pump has to work against all season.
Which way should you install a check valve?
The arrow on the valve body must point in the direction of flow, exactly like the arrow on the pump body, whether the pump is on the flow or return pipe. If both arrows point in the same direction, the check valve is connected to the pump correctly.
On an older system, the arrows may have been painted over or covered with scale. In that case, you can determine the valve’s installation direction by identifying which pipe is the boiler flow and which is the return, and which way the pump pushes water. When the system is running, the flow pipe is noticeably warmer than the return.
Position matters too. A swing check valve works properly only in the positions permitted by the manufacturer, because the flap closes under its own weight. A spring check valve is much less demanding in this respect. Choose the distance from the pump connection in accordance with the valve and pump instructions.
Which check valve for which system?
A correctly installed check valve is, above all, one suited to the type of system. A closed system with a gas boiler is handled differently from a solid-fuel boiler in an open system, and check valves are not used at all in gravity-fed systems.
| System type | Should a valve be installed? | Where | What to watch out for |
|---|---|---|---|
| Closed system, gas or oil boiler with a pump | Only if the boiler does not have one or there are parallel circuits | Downstream of the pump, on the discharge side | Do not duplicate a valve built into the boiler or pump group |
| System with a domestic hot water cylinder charging circuit | Yes, on every pumped circuit | Downstream of the central heating pump and the cylinder charging pump | Spring-loaded valve that prevents gravity circulation to the cylinder |
| Several pumped circuits, mixing valve | Yes, one for each pumped circuit | Downstream of the pump for the circuit in question | Do not install several valves in series |
| Solid-fuel boiler, open system | Yes, while maintaining gravity circulation | Pump on a bypass, gravity valve on the main pipe | Do not block gravity circulation; low pressure and high temperature on the suction side |
| Gravity-fed system without a pump | No | No | The valve creates resistance that can stop circulation |
W pump circuits, spring-loaded valves are most commonly used because the spring closes them regardless of the installation position. We describe valve materials and designs, from brass to cast iron, in the article IBO check valves: types, materials, and applications.
Symptoms of an incorrectly installed check valve
A wrongly installed or faulty valve can be identified by four symptoms: cold radiators while the pump is running, heating after the pump is switched off, a cooling domestic hot water cylinder, and a noisy pump with low flow. Each points to a different cause, so it’s worth distinguishing between them before you start taking the fittings apart.
| Symptom | Most common cause | What to do |
|---|---|---|
| Pump running, radiators cold | Valve installed backwards, no flow | Switch off the pump, isolate and drain the section, and move the valve so it points in the direction of the arrow |
| Radiators heat up after the pump is switched off | Missing or leaking valve, gravity circulation | Check for leaks, clean or replace the insert |
| Domestic hot water cylinder cools down | Backflow between the central heating circuit and the domestic hot water circuit | Spring-loaded valve downstream of the cylinder charging pump |
| Noisy pump, low flow | Valve on the suction side in an open system, dirty valve, or spring that is too strong | Move the valve downstream of the pump and clean it |
Moving the valve requires draining the water: if there are shut-off valves by the pump, simply close them and drain the short section containing the valve. Without them, you need to lower the pressure and drain the water from the system below the valve, then refill and bleed the system after installation.
The first case is the most dangerous. If installed backwards, the pump runs against a closed valve and heats the water in its housing. The motor will not burn out immediately, but you should not leave the pump in this condition for long.
The last symptom can be misleading. When the pump is running at a low speed, a strong spring may only open the valve partially, and the check valve can start restricting flow. If the noise persists despite the valve working properly, the cause may be the pump itself: check the symptoms of a malfunctioning circulation pump.
How do you check a check valve step by step?
You can check the valve in five steps: arrow direction, pipe temperature, test with the pump switched off, cartridge inspection, and bleeding after installation. The first three steps require no tools.
- Compare the arrow on the valve with the arrow on the pump.
- With the pump running, carefully check whether the pipe downstream of the valve is getting warm.
- Switch off the pump and check whether the radiators keep heating up. If they do, the valve is leaking.
- Close the shut-off valves on both sides and drain a small amount of water. If the design allows, remove the cartridge and inspect it. Deposits, limescale and a damaged valve seat are typical causes of check valve failure.
- After reassembly, top up the pressure and bleed the central heating pump after working on the fittings.
Before removing anything, switch off the power to the pump and boiler and wait for the water to cool. The system is pressurized.
Is a check valve needed for a central heating boiler?
It depends on the boiler. For a gas boiler with a built-in pump, check the manual first and see whether the boiler already has a check valve, as one may be factory-installed. With a manually fed boiler, the issue is more serious: a check valve for a central heating boiler must not block the emergency gravity circulation that protects the boiler during a power outage.
Imagine a winter evening: the firebox is full of fuel, and the power suddenly goes out. The pump stops, and the only way to carry heat away from the boiler is gravity circulation. A regular check valve resists gravity, and can practically stop it altogether. The force driving gravity circulation is very small: it is equivalent to the pressure exerted by a column of water just a few centimeters high. A typical check valve spring needs several times more force just to open.
That is why, with solid fuel boilers, the pump is usually installed in a bypass, while a gravity valve remains on the main pipe. When the pump is running, the pressure difference closes it. When the pump stops, the valve opens and water circulates by gravity. A regular pipe in place of the gravity valve cannot do the job, because the pump would keep circulating water through the bypass.
Without an emergency circulation path, a manually fed boiler risks overheating and the system may lose its seal. The layout for such a system should always be selected by an installer. The system described is an open system. A solid fuel boiler can also operate in a closed system, but in that case it is protected against overheating by other devices, such as a safety valve and a cooling valve, which should also be selected by an installer.
Why does a check valve knock?
A check valve usually knocks when the pump starts or stops, as the closing element hits the seat. The most common causes are sediment and limescale on the valve disc, a worn seat, or a swing check valve whose flap rattles with every change in flow.
What helps? First, clean the valve and replace the insert. If a swing check valve is knocking, replacing it with a spring check valve usually works; if the knocking persists, use a damping check valve with soft closing. However, moving the valve before the pump just to quiet it down is not worthwhile.
A thick layer of sediment on the insert is a sign that the problem affects the entire system, not just the valve. In that case, it's worth considering flushing sediment and sludge from the central heating system.
Does a check valve before the pump cause cavitation?
In a closed central heating system, practically not. The resistance of a properly functioning check valve is low compared with the pressure in a typical closed system, which is around 1 to 2 bar. It’s different in a hot open system, where the suction pressure is low and the water temperature is high.
A circulation pump requires a minimum inlet pressure, which increases with the water temperature. For example, the IBO OHI C.O. circulation pump manual gives the following values:
| Water temperature | Minimum inlet pressure | Closed system (approx. 1 to 2 bar) | Open system (often a few tenths of a bar) |
|---|---|---|---|
| below 85°C | 0.05 bar | large reserve | sufficient reserve |
| 90°C | 0.28 bar | large reserve | small reserve |
| 95°C | 0.5 bar | sufficient reserve | real risk of cavitation |
The conclusion is simple: in a closed system, a valve before the pump will not cause cavitation, but it still adds resistance and makes servicing more difficult. W an open system with a manually fed boiler, every bit of resistance on the suction side eats into the already small pressure reserve. The pump can be installed on either the supply or return line, but on the return it operates with cooler water, which, according to the table, requires lower inlet pressure. We discuss pump operating conditions in more detail in our article on installing a central heating circulation pump and its operating conditions.
How many check valves per circuit?
One check valve is enough for one circuit. Each additional valve in series adds resistance and lowers the pump’s operating point, so installing an extra valve as a precaution does not protect anything.
The problem often arises during a retrofit. A pump is added to an old gravity system, while several valves remain on the short circuits. The result: the shortest circuits do not heat up because the pump does not have enough power to open all the valves. Removing unnecessary ones usually restores even heating.
It is also worth remembering that the PN10 or PN16 rating indicates the body’s strength, not its resistance. Resistance is determined by the opening pressure and the Kvs coefficient, and the pressure drop increases with the square of the flow rate.
If the flow is still too weak after removing unnecessary valves, check the pump speed. The maximum head increases with each speed setting: on the IBO OHI C.O. 25-60/180 pump, it is 1 m at the first speed, 3 m at the second, and 6 m at the third. If even the highest speed is not enough, the pump is too weak for this system, and you need to choose a more powerful one from the range of central heating circulation pumps with different heads.
Frequently asked questions
Is it a mistake to install a check valve before the central heating pump?
Not always. W a closed system, a valve before the pump usually will not damage it, although installation on the discharge side is standard because it creates less resistance on the suction side and makes servicing easier. W a hot open system, this installation can cause cavitation.
Is a check valve installed in a gravity system?
No. W a system without a pump, water circulates only because of the temperature difference, and a check valve, especially a spring-loaded one, creates resistance that can stop this circulation.
What are the symptoms of an incorrectly installed check valve?
Four: cold radiators while the pump is running, heating after the pump is switched off, the domestic hot water tank cooling down, and a noisy pump with weak flow.
Is an additional check valve needed on the return to the boiler?
Usually not: a valve after the central heating pump and the domestic hot water charging pump is sufficient. Additional valves in series only add resistance.
How do you install a check valve with a solid-fuel boiler without losing gravity circulation?
The pump is installed in a bypass, while a gravity valve remains on the main pipe and opens when the pump stops. This means that during a power outage, water continues to carry heat away from the boiler, and the installer selects the layout for this type of system.
Can the pump open a check valve?
Yes, a working pump can open one valve without any problem. The problem arises with several valves in series, a strong spring, or a pump running at a low speed.
Does a check valve make it difficult to drain water from the system?
Yes, water will not flow back through the valve. That is why drain valves are planned so that the sections on both sides of it can be drained.
Dambat – a trusted manufacturer of pumps and water engineering equipment with quality certifications.