Zawór mieszający do podłogówki i grzejników - ogrzewanie z jednego kotła

A warm floor in the living room and bathroom, and traditional radiators in the upstairs bedrooms. This combination lets you enjoy the benefits of both systems: underfloor heating provides even, gentle warmth in the living area, while radiators respond quickly to changes in settings in rooms used less often.

Both systems can run on one boiler, even though at first glance they may seem incompatible. Radiators need hot water, while the floor needs considerably cooler water. If water prepared for the radiators flowed straight into the floor loops, the floor would quickly overheat, along with the parquet or laminate flooring.

The mixing system brings these two systems together by lowering the water temperature only for the underfloor heating circuit, while leaving the radiators with the full supply from the boiler. W this article, we explain step by step why it is needed, how it works, what types are available, and how to choose the right one for your home.

Table of contents

  1. Why do underfloor heating and radiators need different temperatures?
  2. How does a mixing system work?
  3. Types of mixing systems: from the simplest to the most advanced
  4. How do you choose a mixing setup for your home and boiler?
  5. How do you set the underfloor heating supply temperature?
  6. Safety thermostat: protecting the floor from overheating
  7. Frequently asked questions

Why do underfloor heating and radiators need different temperatures?

A radiator gives off heat from a small surface area, so it needs hot water. Underfloor heating warms the entire floor surface, so it only needs much cooler water, usually around 30 to 45°C. More importantly, a higher temperature would damage it.

The PN-EN 1264 standard limits the temperature of the floor surface itself, not the water in the pipes. There is a layer of screed and flooring between the pipe and your feet, so the water is always warmer than the floor.

Permitted floor surface temperature according to PN-EN 1264
Zone Maximum surface temperature
Occupied rooms 29°C
Bathrooms 33°C
Perimeter zones along external walls 35°C

However, the boiler delivers water at one temperature. If it is to supply both radiators and underfloor heating, the temperature for the underfloor heating must be lowered separately. That is exactly what the mixing system does.

How does a mixing system work?

The mixing system works on a simple principle: it combines hot water from the boiler with cooler water returning from the underfloor heating loops until it reaches the set temperature. The more cool return water is added to the mix, the lower the underfloor heating supply temperature.

The water flow in a typical system looks like this:

  1. Hot water from the boiler flows to the radiators and the underfloor heating mixing valve.
  2. The mixing valve adds some of the cool water returning from the loops.
  3. The underfloor heating circulation pump pushes the mixed, lukewarm water into the loops in the floor.
  4. The water transfers heat to the floor and returns cooler. Some of it goes back for mixing, while the rest returns to the boiler.

The main components of the system are:

Why does underfloor heating need a separate pump?

The boiler pump pushes water through the boiler and radiators. However, a separate, closed circuit forms after the mixing valve: water circulates between the floor loops and the valve, while hot water from the boiler is added to it in only a small amount. Most of the water in the loops is the same water that has just returned from them and been slightly heated.

This circuit needs its own drive, because the boiler pump cannot push water through the mixing valve and dozens or hundreds of meters of pipes in the floor. Underfloor heating loops create a lot of resistance, while also requiring substantial flow: when the temperature difference between the supply and return is small, each liter transfers less heat than in radiators, so more water has to flow through. Without an additional circulation pump, mixing simply would not work, and the loops would heat poorly or not at all.

W several pumps therefore operate simultaneously in the installation. To prevent one pump from pushing water into the circuit of another, check valves are installed behind the pumps: check valves.

Types of mixing systems: from the simplest to the most advanced

Mixing systems differ in how they regulate temperature and the size of installation they are suited to. Below, we describe them from the simplest, a valve that requires no power, to the most elaborate, a set that serves several circuits. At the end, we mention the RTL valve, which is not a mixing system but is sometimes used in very small zones.

Thermostatic valve with a fixed setting

A thermostatic valve maintains the set supply temperature without electricity. Its thermostatic element automatically adjusts the mixing ratio as the temperature of the water from the boiler changes.

  • Advantages: simple, reliable, no controller required.
  • Disadvantages: does not respond to the weather, so the house may overheat during transitional seasons.

Three-way or four-way valve with actuator

The valve is turned by an electric actuator controlled by a controller with an outdoor temperature sensor. As the temperature outside rises, the controller lowers the underfloor heating supply temperature according to the so-called heating curve. Examples include IBO MIX 3 and MIX 4 mixing valves with a STER-D actuator, which automatically positions the valve when connected to a weather-compensating controller.

  • Advantages: maximum comfort and energy savings, with automatic adjustment to the weather.
  • Disadvantages: requires a power supply and controller, and the heating curve must be set.

Mixing pump group

A pump group combines a mixing valve, circulation pump, thermometers, and shut-off valves in one assembly. It is a ready-to-install module that shortens installation time and reduces the number of connections. One example is the IBO GP PRO 3D-S pump group supplied with an API 25-60/180 pump, featuring a three-way valve and a STER-D actuator that works with an external controller, such as one for a boiler or heat pump. Without an actuator, the IBO GP MIX T pump group is a good choice, with a thermostatic valve set to 20 to 43°C for underfloor heating. Pair it with a pump with a 130 mm connection spacing. It is also worth installing a magnetic filter that protects the pump and valve from sediment upstream of the group.

  • Advantages: quick installation, a tidy boiler room, all components matched to each other.
  • Disadvantages: higher initial cost than a single valve.

Manifold with several pump groups

When an installation has several circuits, e.g. radiators, underfloor heating and domestic hot water tank charging, each gets its own pump group on a shared manifold. Each circuit then operates at its own temperature and with its own pump, while manifolds and pump groups for underfloor heating and central heating bring them together into one well-organized assembly.

  • Advantages: full independence of the circuits, easy to expand.
  • Disadvantages: takes up the most space in the boiler room and requires hydraulic system design.

Mixing-free alternative: RTL valve for a small zone

For a single small loop, e.g. in a bathroom or hallway, an RTL valve is sometimes used instead of a mixing setup. It works differently from a mixer: it does not lower the supply temperature, but limits the temperature of the water leaving the loop. Hot water from the radiator system flows into the loop, and the valve on the return restricts the flow so the water has time to transfer heat to the floor before reaching it.

Since the start of the loop always receives water at radiator temperature, an RTL valve is suitable only for a small area where the floor is intended to improve comfort, not heat the entire room. It is also not a safety device: it acts as a controller and does not shut off the loop if a fault occurs.

  • Advantages: low cost, installation without a pump or controller, simple installation alongside existing radiators.
  • Disadvantages: no mixing, a hot start to the loop, uneven floor temperature, suitable only for small zones.

How do you choose a mixing setup for your home and boiler?

Choosing a mixing setup depends on two things: the size of the underfloor heating system and the type of heat source.

Which mixing setup to choose
Situation Recommended setup
One small loop, e.g. in a bathroom RTL valve (no mixing, small zone only)
Underfloor heating on part of the ground floor, stable heat source Thermostatic valve or group with a thermostatic valve
Large underfloor heating system, condensing gas boiler 3-way or 4-way valve with an actuator and weather compensation control
Solid fuel boiler without a buffer tank Boiler return protection and a separate underfloor heating mixer
Heat buffer tank Thermostatic valve or valve with an actuator, always with a safety thermostat
Several circuits with different temperatures Manifold with pump groups

A condensing boiler achieves its highest efficiency when the return water is cool, below the flue gas dew point, which is around 55°C for natural gas. That’s why it works best with a motorized mixing valve and low radiator temperatures.

A solid-fuel boiler requires a minimum return temperature to prevent corrosion. This is ensured by a separate system, such as a return temperature protection unit for solid-fuel boilers or an IBO MIX TVR thermostatic valve. However, boiler return temperature protection does not replace the underfloor heating mixing valve, as they serve entirely different functions.

If you’re planning to add underfloor heating to an existing radiator system, now is a good time to review the entire boiler room and plan to modernize the heating system and replace the circulation pump.

How do you set the underfloor heating supply temperature?

Set the underfloor heating supply temperature high enough to cover the building’s heat loss on freezing days, but not so high that it exceeds the floor surface temperature limit. W practice, this usually means around 30 to 45°C: a well-insulated home runs closer to the lower end, while an older building runs closer to the upper end.

Two things are worth keeping in mind:

  • The valve setting is the water temperature, not the floor temperature. “40 degrees on the valve” means the floor will be noticeably cooler.
  • A higher temperature won’t heat your home faster. The screed has a high thermal inertia, so raising the supply temperature to 55°C only increases the risk of overheating the floor and damaging the floor covering.

At low supply temperatures, heat output depends primarily on flow rate, so the underfloor heating circulation pump should run in a mode suited to the system. Since it runs throughout the heating season, it’s worth choosing an energy-efficient central heating circulation pump, which uses little electricity under this kind of load.

Safety thermostat: protecting the floor from overheating

A mixing valve regulates the temperature, but it is not a safety device. If the valve insert fails, the controller malfunctions, or the valve gets stuck, hot water straight from the boiler may enter the loop. That is why a safety thermostat, usually a strap-on type, is installed on the underfloor heating supply; it switches off the underfloor heating pump when the set temperature is exceeded.

Not every pump group comes equipped with a safety thermostat, so it is often installed separately. Its setting is selected according to the design and the requirements of the underfloor heating system manufacturer.

Warning: water in the floor that is too hot. An overheated floor can damage parquet and laminate flooring, put stress on the screed, and exceed the pipes' permissible operating parameters. Never connect an underfloor heating loop directly to the radiator supply, and have the thermostat's electrical connection handled by a qualified professional.

Frequently asked questions

Can underfloor heating and radiators be supplied by the same boiler?

Yes, provided the underfloor heating circuit has a mixing system that lowers the water temperature only for the floor.

How does a mixing valve for underfloor heating work?

It combines hot water from the boiler with cooler water returning from the loop until it reaches the set floor heating supply temperature.

What should the water temperature be in underfloor heating?

Usually around 30 to 45°C for the supply temperature. The exact value is determined by the design and heating curve.

Is 45°C too high for underfloor heating?

Not always, because 45°C is within the typical range. The deciding factor is the floor surface temperature, which should not exceed 29°C in living areas.

Is a thermostatic valve enough for underfloor heating?

Yes, with a stable heat source and a small or medium-sized underfloor heating system. With a modulating boiler and a large area, a valve with an actuator and weather-compensated control is a better choice.

Is an RTL valve enough to heat an entire room?

Usually not. An RTL valve does not mix the water; it only limits the return temperature from the loop, so it works well in a small area, such as a bathroom. Larger areas require a mixing system.

Does an RTL valve protect the floor from overheating?

No. An RTL valve regulates the flow through the loop, but it does not switch off the pump or shut off the loop in the event of a fault. A safety thermostat provides this protection.

Does underfloor heating need a safety thermostat?

Yes. A mixing valve is not a safety device, and the thermostat switches off the pump if water that is too hot enters the loop.