Complete domestic wastewater pumping station consisting of a tank, a three-phase sewage pump with a grinder, and a local control system.
The supplied pumping station is ready for pump installation and commissioning. The tank is equipped with connection outlets for the wastewater inlet and discharge. The pump can be easily installed in or removed from the tank together with the piping, thanks to the system cast-iron coupling.
The pumping station can be used to pump wastewater from septic tanks, single-family homes, offices, and small industrial facilities. It can be used both to pump wastewater into gravity drainage wells and into pressurized pipelines (up to 1.5–2 bar).
The basic control system ensures automatic pump operation and provides optical and audible notification when the maximum wastewater level in the tank is exceeded.
Tank:
Control system:
- Start float switch
- Overflow float switch indicating that the alarm level in the pumping station has been exceeded
- Thermal pump protection
- Optical and audible alarm system indicating pumping station overflow, powered by low-voltage 12 V with Type B protection
- Residual-current protection
- Surface-mounted IP65 control cabinet
- Operation-0-Manual switch
- Phase failure and phase asymmetry sensor
- Voltage-reducing transformer to 12 V
Fittings:
- DN50 cast-iron check valve
- DN50 ball shut-off valve
- DN50 cast-iron coupling
- AISI 304 DN50 pipeline
- d63 discharge outlet (fitting)
- d160 inlet outlet (socket)
Pump:
- IBO KRAKEN 1800 DF
- Pump with stainless steel grinder
- Three-phase, 1.8 kW, 10 m cable
- Head: 5–25 m
- Capacity: 3–18 m³/h
- Weight: 35 kg