IW series antifreeze valves are designed for installation in systems using monobloc heat pumps to protect them against fluid thickening and freezing. The three-piece design simplifies servicing—a shut-off valve is installed between the valve body and the insert.
Features
- Brass body and thermal element,
- Operation within a narrow temperature range,
- The shut-off valve ensures reliable, leak-tight isolation,
- Operates only in response to temperature changes,
- Unaffected by pressure changes,
- Easy installation using a pipe wrench • Removes the minimum amount of water required to prevent damage caused by freezing.
Parameters
- Dimensions: 107 × 58 × 1”,
- Connection: 1”,
- Medium: water,
- Operating range (medium): 0°C–65°C,
- Operating range (ambient temperature): -30°C–65°C,
- Valve activation temperature (medium): 3°C,
- Closing temperature (medium): 4°C,
- Fully open valve: 1°C
- Maximum flow rate: 10 m³,
- Maximum drainage rate: 1 m³/h,
- Maximum pressure: 8 bar.