IBO MIX T thermostatic mixing valves are intended for water installations where temperature stabilization is required.
Technical specifications
- Operating temperature: 20–43°C
- Maximum operating temperature: 95°C (110°C for short periods)
- Outlet mixing accuracy: +/- 2°C
- Recommended operating pressure: 3 bar
- Maximum static pressure: 10 bar
- Maximum operating pressure: 5 bar
- Maximum pressure difference at the connections: 3 bar
- KVS flow rate: 1.6 m3/h
- Medium: Water, water/glycol solution up to 30%