Anti -IW series Anti -I and are intended for installation in installations where monoblock heat pumps are used to protect them against thickening the factor and freezing it. The three -part construction simplifies service work - a stop valve is installed between the valve body and the insert.
Characteristics
- Body and thermal element from brass,
- Work in a narrow temperature range,
- The alloy valve provides reliable, tight cut,
- Operation only under the outflow of a temperature change,
- Lack of impact of pressure changes,
- Easy installation using a pipe key • Removes the minimum amount of water required to prevent damage caused by freezing.
Parameters
- Dimensions: 115 × 58 × 1-1/4 ",
- Connection: 1-1/4”,
- Medium: water,
- Work range (medium): 0 ° C -65 ° C,
- Operating range (external temperature): -30 ° C -65 ° C,
- Valve operation temperature (medium): 3 ° C,
- Closing temperature (medium): 4 ° C,
- Full opening of the valve: 1 ° C
- Maximum flow: 16 m³,
- Maximum drain 1 m³/ h,
- Maximum pressure 8 bar.